- Contact Person : Ms. Zhang Doreen
- Company Name : Guangdong East Power Co., Ltd.
- Tel : 86-769-22898802
- Fax : 86-769-87920552
- Address : Guangdong,Dongguan,No. 6, Northern Industry Road, Songshan Lake, Sci & Tech, Industry Park, Dongguan City, Guangdong Province. China
- Country/Region : China
- Zip : 523808
Related Product Searches:rectifier -Powercell 1U,High Quality,rectifier, Switching Mode Power Supply,Powercell 1U 48V/2000W
DC Output | |
Voltage | 53.5 VDC(adj.range:43.5-57.6 VDC) |
Output Power | 2000W at nominal input |
Maximum Current | 41.7 Amps at 48 VDC and nominal input |
Current Sharing | ±5% from true average current between modules |
Static voltage regulation | 0.5% from 10% to 100% load |
Dynamic voltage regulation | 5.0% for 10-90% load variation, regulation time< 50ms |
Hold up time | >20ms;output voltage >43.5 VDC at 1500W load |
Ripple and Noise | < 100 mV peak to peak, 30 MHz band with <0.96mV rms psophometric |
Output Protection | Over voltage shutdown Blocking diode Short circuit proof High temperature protection |
AC Input | |
Voltage | 85-300 VAC(Nominal 185-275 VAN) |
Frequency | 45 to 66Hz |
Maximum Current | 12.8Arms maximum at nominal input and full load |
Power Factor | >0.99 at 20% load or more |
Input Protection | Varistors for transient protect mains fuse in both lines Disconnect above 300VAC |
Other Specifications | |
Efficiency | Typical 92% , min. 91% at 40-90% load |
Isolation | 3.0 KVAC-input and output 1.5 KVAC-input earth 0.5 KVDC-output earth |
Alarm | Low mains shutdown High temperature shutdown Rectifier Failure Over voltage shutdown on output Fan failure, one or two fans Low voltage alarm at 43.5V CAN bus failure |
Warnings | Low temperature shutdown Rectifier in power derate mode Remote battery current limit activated Input voltage out of range, flashing at over voltage Loss of CAN communication with control unit, stand alone mode |
Visual indications | Green LED:ON, no faults Red LED: rectifier failure Yellow LED: rectifier warming |
Operating temp | -40 to +75°C(-40 to +158°F) |
Storage temp | -40 to +85°C(-40 to +185°F) |
Cooling | 2 fans(front to back airflow) |
Fan Speed | Temperature and current regulated |
MTBF | >350,000hours Telcordia SR-332 Issue l, method III(a)(T ambient : 25°C) |
Acoustic Noise | <55dBA at nominal input and full load (T ambient < 30°C) |
Humidity | Operating: 5% to 95% RH non-condensing Storage:0% to 99% RH non-condensing |
Dimensions | 109×41.5×327mm(w*h*d) (4.25×1.69×13) |
Weight | 1.9kg(4.19lbs) |
Applicable standards | |
Electrical safety | IEC 60950-1 UL 60950-1 CSA 22.2 |
EMC | ETSI EN 300 386 V.1.3.2 (telecommunication network) EN 61000-6-1(immunity, light industry) EN 61000-6-2(immunity, industry) EN 61000-6-3(emission, light industry) EN 61000-6-4(emission, industry) Telcordia NEBS GR1089 CORE |
Harmonics | EN 61000-3-2 |
Environment | ETSI EN 300 019-2(-1,-2,-3) ETSI EN 300 132-2 Telcordia NEBS GR63 CORE Zone 4) RoHS compliant (pending) |
rectifire